DC Fan Control and Monitoring: FG, RD and PWM Signals Explained
For example, a power supply or industrial control system may increase fan speed as its internal temperature rises. The controller then needs to know whether the fan is actually running at the expected speed. If the rotor becomes locked, the system may also need an alarm signal to trigger a response.
These requirements involve three commonly available DC fan functions: PWM, FG and RD.
PWM (Pulse Width Modulation) controls fan speed through an external pulse signal.
FG (Frequency Generator) provides speed feedback through output pulses.
RD/RRD provides an alarm output indicating a fan operating condition, such as a locked state.
Although these functions are often discussed together, they serve different purposes in a cooling system. Understanding their electrical characteristics and how they interact with an equipment controller helps OEM engineers select the appropriate fan configuration.
This guide explains how FG, RD and PWM work, what their output signals mean, and which specifications should be checked before integrating a DC fan into an electronic or industrial device.
1. What Are FG, RD and PWM Signals in DC Fans?
FG, RD and PWM are three different fan functions that support speed control and operating-status monitoring. They can be used to connect a DC cooling fan with the control system of the equipment in which it is installed.
| Function | Full Name | Main Purpose | Typical Application |
|---|---|---|---|
| FG | Frequency Generator | Provides rotational speed feedback | Fan RPM monitoring |
| RD | Alarm High | Provides an alarm output | Fan locked-state detection |
| RRD | Alarm Low | Provides an alternative alarm output | Fan locked-state detection |
| PWM | Pulse Width Modulation | Controls fan speed | Automatic cooling adjustment |
The main difference is the direction of the signal.
PWM is an input to the fan. The controller sends a pulse signal to request a particular operating speed.
FG and RD/RRD are output functions. They provide information from the fan to the external control circuit.
A controller can therefore use PWM to adjust fan speed, FG to monitor rotational speed and RD/RRD to receive a defined alarm output. The availability of these functions depends on the selected fan model and configuration.
FG for Fan Speed Feedback
FG generates electrical pulses related to fan rotation. By measuring the frequency of these pulses, a controller can calculate the fan's rotational speed.
This function is useful when equipment needs to monitor whether a cooling fan is operating within its expected speed range.
RD/RRD for Fan Status Detection
RD and RRD provide different alarm output configurations. In YCCFAN's function documentation, they are illustrated as Alarm High and Alarm Low outputs.
They allow an external circuit to identify a defined fan condition, including the locked state shown in the documentation.
PWM for Fan Speed Control
PWM controls fan speed through a pulse signal. By changing the duty cycle, the controller can adjust the fan's operating speed according to the equipment's cooling requirements.
Unlike FG, which reports operating speed, PWM provides the control command.
2. How Does FG Tachometer Feedback Work in a DC Fan?
An FG signal, also called a tachometer signal, allows an external controller to monitor fan rotation without relying only on the fan's power consumption or operating command.
The fan generates electrical pulses as it rotates. The external circuit receives these pulses and measures their frequency to determine rotational speed.
FG Signal Output Circuit
YCCFAN's FG function documentation illustrates an open-collector output circuit.
In this arrangement, the fan's internal output transistor switches the FG signal line toward ground. An external pull-up resistor is used in the customer's circuit to establish the high-level voltage when the transistor is not conducting.
The basic connection includes:
- FG output from the fan.
- An external pull-up resistor.
- A suitable voltage source (Vcc).
- An output connection to the customer's controller.
- A common electrical reference as required by the circuit design.
The technical documentation specifies the following output limits:
| Parameter | YCCFAN Documentation |
|---|---|
| Output structure | Open-collector circuit |
| Maximum collector-emitter voltage (Vce) | 0.7V |
| Maximum Link current | 5mA |
| External circuit | Pull-up resistor required |
| Maximum Vcc operating voltage | Must be confirmed for the selected configuration |

The resistor value should be selected according to the controller's input voltage, the fan output's electrical limits and the required signal characteristics.
The pull-up supply must not exceed the permitted operating voltage of the output circuit. The customer should also ensure that the current through the output transistor remains within the specified limit.
Understanding FG Output Waveforms
When the fan operates normally, the FG output produces pulses corresponding to its rotation.
YCCFAN's function documentation also illustrates two possible locked-state waveform behaviors:
- The output may remain at a high level after the fan enters the locked state.
- Alternatively, it may remain at a low level.
These are two illustrated output configurations, not a universal behavior that should be assumed for every fan model.
The selected output configuration needs to be confirmed before the controller's monitoring logic is designed.
How to Calculate Fan RPM from FG Signals
The controller can calculate fan speed by measuring the frequency of the FG pulses.
The general calculation is:
RPM = (60 x f) / PPR
Where:
- RPM = revolutions per minute.
- f = measured FG pulse frequency in Hz.
- PPR = pulses generated per revolution.
For example, if the controller measures an FG frequency of 100 Hz, the RPM calculation depends on the actual PPR specified for that fan.
A two-pulse-per-revolution fan and a one-pulse-per-revolution fan will produce different RPM readings at the same signal frequency.
This is why OEM engineers should not assume that all DC fans use the same PPR. The actual value must be confirmed from the selected model's technical specifications.
3. How Does RD Fan Alarm Detection Work?
While FG provides information about rotational speed, an alarm output provides another way for the controller to identify a defined fan condition.
YCCFAN's function documentation illustrates two alarm configurations: RD Alarm High and RRD Alarm Low.

RD Alarm High Output
The RD Alarm High configuration uses a high-level output to indicate the locked state shown in the technical waveform.
The controller can monitor the signal and use the corresponding state to trigger an alarm or other protective response.
RRD Alarm Low Output
The RRD Alarm Low configuration uses a low-level output to indicate the locked state.
This provides an alternative signal logic for systems designed to detect a low-level alarm condition.
The choice between these configurations depends on the control circuit and the alarm logic required by the equipment.
FG vs. RD: Speed Feedback or Fault Detection?
FG and RD should not be treated as interchangeable functions.
| Comparison | FG | RD/RRD |
|---|---|---|
| Main purpose | Speed feedback | Alarm output |
| Signal behavior | Pulse output during operation | High or low alarm state |
| Monitoring focus | Rotational speed | Defined abnormal operating condition |
| Controller function | Calculate or monitor RPM | Identify an alarm condition |
| Typical use | Speed monitoring | Fan protection and equipment alarms |
For an OEM cooling system, FG is useful when the controller needs actual rotational-speed information. RD/RRD is useful when the controller needs a separate signal to identify a specified fan condition.
Using both functions can provide more information than relying on a single operating signal, provided the selected fan supports the required configuration.
4. How Does PWM Control DC Fan Speed?
PWM allows a controller to adjust fan speed without continuously changing the fan's supply voltage.
Instead, the controller sends a pulse signal. The proportion of time that the signal remains high within each cycle is called the duty cycle.
Changing the duty cycle changes the fan's speed response.
PWM Frequency and Voltage Requirements
YCCFAN's PWM function documentation provides the following electrical parameters:
| Parameter | Specification |
|---|---|
| PWM Frequency | 300Hz-30kHz |
| PWM Duty Cycle | 0%-100% |
| Pulse High Voltage | 2.8V-10V |
| Pulse Low Voltage | ≤0.6V |

These values describe the PWM input requirements shown in the supplied technical documentation.
The controller's output should be checked against these requirements before connecting it to the fan.
How Does PWM Duty Cycle Affect Fan Speed?
The duty cycle represents the percentage of each PWM period during which the signal is high.
The calculation is:
Duty Cycle = (Ton / T) x 100%
- Where:
- Ton = time the pulse remains high.
- T = total PWM period.
For example, a 50% duty cycle means that the signal remains high for half of each cycle.
However, a 50% duty cycle does not necessarily mean that the fan runs at 50% of its rated RPM.
The relationship between duty cycle and rotational speed depends on the fan's control characteristics.
YCCFAN's function documentation includes three PWM-to-RPM response curves. These curves illustrate that the starting region and speed response may differ depending on the control configuration.

For OEM applications, engineers should use the relevant model-specific performance information rather than assume a universal linear relationship.
Understanding PWM Speed Response Curves
When evaluating a PWM-controlled fan, it is useful to examine more than the maximum rated speed.
The following points should also be considered:
- Minimum operating speed.
- Starting behavior at low duty cycles.
- Speed response as the duty cycle increases.
- Whether the fan maintains stable operation across the intended control range.
- These factors matter when the equipment needs different cooling levels under different operating loads.
The actual PWM response curve should be confirmed for the selected fan model and configuration.
5. How Do FG, RD and PWM Work Together in OEM Equipment?
In an electronically controlled cooling system, PWM, FG and RD/RRD can serve three complementary functions.
PWM sends the speed command, FG reports rotational-speed information, and RD/RRD provides an alarm output for a defined abnormal condition.
Consider an industrial electronic enclosure where heat generation changes according to equipment load.
When the internal temperature increases, the controller may request a higher fan speed through PWM. The FG output allows the controller to monitor whether the fan is rotating at the expected speed. If the fan enters a locked condition, the configured RD/RRD output can provide an alarm signal.
The system can then use its own control logic to decide whether to display a warning, activate protection or take another action.
Fan Speed Control and Feedback
PWM and FG perform different tasks within the same control loop.
The controller sends a PWM command to adjust the fan's speed. The FG output provides feedback that can be compared with the expected operating range.
This helps engineers distinguish between a commanded speed and the actual rotational speed reported by the fan.
Monitoring Fan Status and Abnormal Conditions
FG and RD/RRD can provide different types of information.
A controller may use FG to identify an unexpected RPM change and RD/RRD to detect a defined locked-state condition.
The exact alarm response should be determined by the equipment designer. The fan's output signal alone does not define the complete protection strategy.
Integrating Fan Signals with Equipment Controllers
Before integrating the fan into an equipment control board, engineers should verify:
- Whether the controller supports the fan's FG output type.
- Whether the pull-up voltage is compatible with the fan output.
- Whether the RD/RRD alarm logic matches the controller's input logic.
- Whether the PWM frequency and voltage levels meet the fan's requirements.
- Whether the selected fan model supports all required functions.
A fan may have the correct dimensions and rated voltage but still require additional interface design to work with the equipment's control system.
For this reason, electrical compatibility should be checked alongside airflow, static pressure and installation requirements.
6. What Should OEMs Check When Selecting a DC Fan with FG, RD or PWM?
Selecting a DC fan for an OEM project involves more than choosing a fan with the required control functions. For a broader purchasing overview, see DC Fan Manufacturer vs Distributor: Which Should OEM Buyers Choose.
The fan must also match the equipment's electrical system, installation space and cooling requirements.
Electrical Compatibility and Signal Requirements
Start by identifying the signals required by the equipment controller.
| Selection Item | Information to Confirm |
|---|---|
| Rated Voltage | 5V, 12V, 24V or other available configuration |
| Rated Speed | Required operating RPM |
| FG Output | Whether speed feedback is needed |
| PPR | Actual pulses per revolution |
| RD/RRD | Required alarm output logic |
| PWM Frequency | Controller output frequency |
| PWM Voltage | High and low signal levels |
| Connector | Connector type and pin configuration |
The controller's input and output characteristics should be compared with the fan's electrical specifications before the final model is selected.
Fan Speed, Airflow and Static Pressure
Control functions do not replace the basic cooling requirements.
A fan with FG and PWM capabilities still needs to provide sufficient airflow and static pressure for the equipment.
Engineers should evaluate:
- Available installation dimensions.
- Required airflow.
- Airflow resistance inside the equipment.
- Operating speed range.
- Noise requirements.
- Operating temperature.
For equipment with restrictive airflow paths, the fan's performance curve is particularly important.
Connector, Pinout and Function Configuration
The connector and pin assignment must be confirmed for the exact model.
Do not assume that the wire colors or pin positions are identical across different manufacturers or product series.
For customized configurations, the OEM should provide the required power, FG, RD/RRD and PWM connections so the manufacturer can confirm the appropriate electrical arrangement.
What Should Be Verified During Sample Testing?
Before approving a fan for mass production, it is useful to test it under the intended equipment conditions.
A practical verification process includes:
- Confirming the rated voltage and current.
- Checking fan startup and operating behavior.
- Measuring the FG output waveform.
- Verifying the RPM calculation against the specified PPR.
- Checking the RD/RRD alarm response under the specified test conditions.
- Testing PWM speed response across the intended duty-cycle range.
- Confirming stable operation within the equipment's cooling system.
This helps identify electrical interface issues before the fan is integrated into a larger production system. For certification-related verification, refer to our guide on cooling fan requirements for UL 508A control panels.
7. YCCFAN DC Fans with FG, RD and PWM Function Options
YCCFAN offers DC axial cooling fans with different dimensions, voltage configurations and optional control functions for OEM applications.
One example is the DC2507F series, a compact fan measuring 25 x 25 x 7 mm.
DC2507F - Compact DC Axial Fan
The DC2507F product documentation lists the following construction and function information:
| Specification | Product Information |
|---|---|
| Size | 25 x 25 x 7 mm |
| Construction | Glass-fiber-reinforced plastic |
| Impeller and Housing | PBT, UL 94V-0 rated |
| Operating Temperature | -10°C to +70°C |
| Function Options | FG, RD, PWM, Auto Restart, Polarity Protection |
The associated specification table lists different 5V and 12V model configurations, with rotational speeds ranging from 5,000 to 14,000 RPM.
These values correspond to different product variants and should not be interpreted as one fan operating across the entire range.
The FG, RD and PWM functions provide options for projects that require speed feedback, alarm outputs or external speed control.
Function Options for OEM Cooling Applications
For OEM projects, the required fan configuration depends on how the equipment controller manages cooling.
Some applications may only require PWM speed control. Others may need FG feedback to monitor rotational speed or an RD/RRD output for alarm detection.
When selecting a fan, it is important to confirm the complete model number and the specific function combination.
YCCFAN's technical team can help review the required voltage, operating speed, installation dimensions and signal functions to identify a suitable configuration.
For projects requiring customized fan functions, engineers should provide the controller's electrical requirements and connector information during the initial evaluation.
Explore the YCCFAN DC Fan Product Range or visit the Technical Downloads section to review available product documentation.
If you are developing an electronic or industrial device that requires speed feedback, alarm monitoring or PWM speed control, contact YCCFAN to discuss the required fan configuration.
8. FAQs About DC Fan Control Signals
1. What is the difference between FG and RD signals in a DC fan?
FG provides pulse signals related to fan rotation, allowing a controller to monitor rotational speed. RD/RRD provides an alarm output that indicates a defined fan condition, such as a locked state. FG is primarily used for speed feedback, while RD/RRD is used for status or fault monitoring.
2. How does a DC fan tachometer signal work?
A DC fan tachometer signal, commonly called FG, generates electrical pulses related to fan rotation. The controller measures the pulse frequency and uses the specified pulses per revolution (PPR) to calculate the fan's RPM.
3. Does an FG signal require an external pull-up resistor?
For an open-collector FG output, an external pull-up resistor is generally required to establish the high-level signal voltage. The resistor value and supply voltage must be compatible with the fan's electrical limits and the controller's input requirements.
4. How do you calculate fan RPM from a tachometer signal?
RPM can be calculated using the measured pulse frequency and the fan's specified PPR:
RPM = (60 x f) / PPR.
The actual PPR must be obtained from the specific fan's technical documentation.
5. What happens when a DC fan is locked?
A locked fan cannot maintain normal rotation. Depending on its protection configuration, the fan may reduce its current, stop operating temporarily and attempt to restart. An available FG or RD/RRD output may also provide information about the locked condition.
6. Can PWM control and FG speed feedback work together?
Yes, a fan configuration can support both PWM speed control and FG speed feedback. PWM provides the speed command, while FG reports rotational-speed information. Their electrical compatibility and simultaneous availability should be confirmed for the selected fan model.
7. What is the difference between RD Alarm High and RD Alarm Low?
RD Alarm High and RD Alarm Low describe different alarm output logic configurations. In YCCFAN's function documentation, the locked state is represented by a high-level output in the RD configuration and a low-level output in the RRD configuration. The required logic should match the controller's input design.
8. What information should OEMs provide when ordering a DC fan with FG and PWM functions?
OEMs should provide the required fan dimensions, rated voltage, target RPM, airflow, static pressure, FG output requirements, PPR, PWM frequency, voltage levels, connector and pinout requirements. If an alarm output is needed, the required RD/RRD logic should also be specified.
Technical Note: The FG, RD/RRD and PWM electrical values in this article are based on the YCCFAN function documentation supplied for reference. Actual signal configurations, complete model numbers, PPR values, output voltage limits and available combinations should be verified against the applicable product specification before design approval or mass production.